Performance evaluation and modeling of a hybrid cooling system combining a screw water chiller with a ground source heat pump in a building | |
---|---|
Year of publication | 2010 |
Title of paper | Performance evaluation and modeling of a hybrid cooling system combining a screw water chiller with a ground source heat pump in a building |
Author | 전종욱 , 이선일 , 홍대희 , 김용찬 |
Publication in journal | |
Publication date | |
Volume & other data | |
Abstract | The performance of a hybrid cooling system that combines a screw water chiller with a ground source heat pump (GSHP) was measured and analyzed at various cooling loads. In addition, the hybrid cooling system in a building was modelled sophisticatedly using EnergyPlus and then validated with the measured data. The coefficient of performance of the GSHP was lower than that of a conventional chiller in the monitored building, but the hybrid cooling system helped to stably provide the required cooling capacity at high-load conditions. The mean bias error and the normalized root-mean squared error of the predicted cooling load of the building were 8% and 12.4%, respectively. The hybrid cooling system was simulated by varying four operating parameters: the operating schedule, chilled water temperature (TCW), dry-bulb temperature (TDB), and entering water temperature (TEW). The TCW is ascertained as being the most effective control parameter in the hybrid cooling system. |